single-produkty.php
PRODUCTS

SoliTherm Outdoor

Outdoor conditions can be harsh on control cabinets, therefore our units are thoroughly designed to protect your cabinets against any ingress of foreign solid and/ or liquid material that could potentially damage the sensitive electronic components. The high fin separation nanocoated condenser requires almost no maintenance and service.
Our wall mounted cooling units operate between −20°C and 55°C. An optional heater kit is available to heat the internal cabinet temperature when necessary.

All SoliTherm Outdoor cooling units are equipped with our new electronic controller, which constantly monitors the pre-set cabinet temperature. Depending on the temperature and the power loss inside the cabinet, the cooling or heating circuits will be switched on and off accordingly.

Energy saving and extended component life are the positive effects. The SoliTherm Outdoor range offers cooling capacities from 550 W up to 4 kW and has as a standard protection rating towards the cabinet of IP56 (NEMA 12, 3, 3R, 4 and 4X). Full stainless steel versions even meet the NEMA 4X requirements. All units come with a cover in steel, powder coated (RAL 7035).

Optional stainless steel covers are available for improved corrosion protection.
The efficient outdoor solution
  • IP protecton according to IEC 60 529; External /Internal: IP56

  • Operating temperature range: −20°C –+55°C

Send inquiry

    Hide the table
    No.
    1
    2
    3
    4
    5
    6
    7
    8
    9
    10
    11
    12
    13
    14
    15
    16
    17
    18
    19
    20
    21
    22
    23
    24
    25
    26
    Dimensions
    (width x height x depth, mm)
    250 × 480 × 190
    320 × 600 × 110
    315 × 830 × 270
    315 × 830 × 270
    315 × 830 × 270
    315 × 830 × 270
    315 × 830 × 270
    315 × 830 × 270
    315 × 830 × 270
    315 × 830 × 270
    315 × 830 × 270
    315 × 900 × 270
    315 × 900 × 270
    315 × 900 × 270
    395 × 1150 × 270
    395 × 1150 × 270
    395 × 1150 × 270
    395 × 1150 × 270
    395 × 1150 × 270
    395 × 1150 × 270
    457 × 1550 × 355
    457 × 1550 × 355
    457 × 1550 × 355
    457 × 1550 × 355
    457 × 1550 × 355
    457 × 1550 × 355
    Type – Cooling capacity
    L35L35 / L35L50 (DIN 3168)
    OC 5704 – 290 W / 250 W
    OC 4269 – 380 W / 120 W
    OC 5705 – 550 W / 410 W
    OC 5705 – 550 W / 410 W
    OC 5705 – 550 W / 410 W
    OC 5708 – 750 W / 470 W
    OC 5708 – 750 W / 480 W
    OC 5708 – 750 W / 480 W
    OC 5709 – 850 W / 610 W
    OC 5709 – 850 W / 600 W
    OC 5709 – 850 W / 600 W
    OC 5710 -1 kW / 660 W
    OC 5710 -1 kW / 660 W
    OC 5710 – 1 kW / 720 W
    OC 5715 – 1,5 kW / 1,22 kW
    OC 5715 – 1,5 kW / 1,22 kW
    OC 5715 – 1,5 kW / 1,22 kW
    OC 5720 – 2 kW / 1,6 kW
    OC 5720 – 2 kW / 1,6 kW
    OC 5720 – 2 kW / 1,63 kW
    OC 5726 – 2,5 kW / 1,97 kW
    OC 5726 – 2,5 kW / 2 kW
    OC 5726 – 2,5 kW / 2 kW
    OC 5731 – 3 kW / 2,4 kW
    OC 5731 – 3 kW / 2,4 kW
    OC 5731 – 3 kW / 2,4 kW
    Voltage / Frequency
    230 V – 50/60 Hz
    230 V – 50/60 Hz
    230 V – 50/60 Hz
    120 V – 60 Hz
    400/460 V – 50/60 Hz 2~
    230 V – 50/60 Hz
    120 V – 60 Hz
    400/460 V – 50/60 Hz 2~
    230 V – 50/60 Hz
    120 V – 60 Hz
    400/460 V – 50/60 Hz 2~
    230 V – 50/60 Hz
    120 V – 60 Hz
    400/460 V – 50/60 Hz 2~
    230 V – 50/60 Hz
    120 V – 60 Hz
    400/460 V – 50/60 Hz 2~
    230 V – 50/60 Hz
    120 V – 60 Hz
    400/460 V – 50/60 Hz 3~
    230 V – 50/60 Hz
    120 V – 60 Hz
    400/460 V – 50/60 Hz 3~
    230 V – 50/60 Hz
    120 V – 60 Hz
    400/460 V – 50/60 Hz 3~
    X