single-produkty.php
PRODUCTS

Base separator – Safety transducer

Base separator - safety transducer (3A) on DIN rail - safety class SIL 3 (TUV)
Application

Ensures insulation input / output. Processing of the lock signal from the system, mushroom breaker, etc. to SPDT NO transducer with loading 3A. Control of the safety circuits (e.g. locking electrovalves, emergency breakers, etc.)

SIL function

Implements SIL 3 function for NE or ND loading
– for NE loading, it shuts them down by switching off the input
– for ND loading, it switches them on by switching on the input

Send inquiry

    Technical data:

    Hide the table
    No.
    1
    2
    3
    4
    5
    6
    7
     
    Input signal
    Output signal
    Power supply
    Attestations
    Characteristic
    Safety class SIL (Safety Integrity Level)
    Options / functions
     
    20.4...27.6 Vdc, protection against reverse polarization
    DPST NO transducer, max. parameters: 3A 250Vac 750VA, 3A 125Vdc 120W
    (resistance load) / reaction time 3 ms / max. 10 Hz
    Input loop supply
    ATEX- IMQ 09 ATEX 013X, ,FM & FM-C, TUV certificate SIL3 acc. to IEC61508
    Ex II 3G nAC IIC T4
    SIL3 even up to 10 years (TUV certificate No. C-IS-183645-01)
    Single-channel D1092S or double-channel D1092D version
    X